The June 25, 1998 blackout report needs to be on the interwebs available to the world.

June 25, 1998? That’s the night of the transmission fail that disconnected the Midwest from the Eastern Interconnect. That question was asked by Minnesota Power’s attorney of each and every witness, I think other than MP, but maybe MP witnesses too, in the Arrowhead transmission project hearing, circa 1999-2000. There were cries of “Hospitals will go dark without the Arrowhead project,” “We’re going to freeze in the dark in an incubator” which became “We’re going to freeze in the dark on a respirator without a job” — it was so histrionic.

The Arrowhead transmission project was project 13J of the WRAO Report, and the WIREs Report, which presented many transmission lines, but chose the Arrowhead transmission project as the “be all and end all” of transmission in the Midwest, that it would fix all the transmission problems:

The hearing went forward, 2 weeks in Minnesota, where MP got an exemption from Minnesota Power Plant siting law, and for TWO MONTHS in Wisconsin, for Round 1, then 2 weeks after the cost went way up, and another 3-5 days of hearing later when cost went up again. They got their permit, it’s up…

But in that first hearing, I did get to introduce the report that showed that the June 25, 1998, blackout was NOT caused by too little capacity, it was not caused by an unreliable transmission system. It was caused by corporate greed, transmission operators running the Prairie Island-Byron 345kV’s TCEX flow over the limit, disregarding operating guides, and disregarding requests and demands to ramp the power down, violating MAPP Operating Standards and NERC Operating Policies. SHAME, NSP, SHAME!!! And MP was so tacky, trying to attribute their desire for bulk power transfer to the blackout, that the Arrowhead project would save us. Yeah, right…

Here’s the report, below, it’s a gem, I’m posting this today because I’m shoveling off my desk and there are a lot of gems here, so posting them will get them out into the world in perpetuity — can’t disappear something from the internet! Scanning them in is taking a while, a royal and dusty pain in the patoot, but just for you inquiring minds, HERE IT IS:

Here are a couple snippets, starting with p. 2:

Bottom line?

OPERATE WITHIN OPERATING GUIDE LIMITS!!

DOH!

The report goes on and on with stupid human tricks – the flow was NOT reduced by NSP System Operators:

From pps 10-11:

So if the operators had been doing the job, not focused on keeping that line operating with all that power flowing through it, selling that power, the blackout may not have happened. Great…

And for some reason, NSP operators were not communicating:

300 MW above the operating guide limits:

OPERATE WITHIN OPERATING GUIDE LIMITS!! DOH!

Operator error is a too-generous way to put it — but for the efforts to NOT reduce power flows, the inadequate response of system operators and their failure to communicate the degree of the problem, the blackout may not have happened. And then utilities have the nerve to say that because of the June 25, 1998 blackout, we need the 13j Arrowhead transmission project?

How many years have I been saying that the purpose of this massive transmission build-out is to market coal elsewhere? Decades, folks, it’s been decades… And this latest from Xcel Energy, Notice of Comment period just out today, is demonstration that they plan to keep running those coal plants and selling it. Will the Public Utilities Commission care?

Here’s the newly released Xcel Energy plan, and a comment period:

The plan?

Here’s the Notice:

What to comment about? From the Commission’s Notice:

Bulk power transfer was the whole point of the transmission build-out, to be able to sell anything generated at any Point A to any Point B. And then coal generated here could be sold elsewhere, eastward via transmission, while we use generation that isn’t quite so dirty (but that’s dirty in its own way). We’re so clean here in Minnesota… NOT! We’ve been a pass through for Dakotas’ coal for a while, and now, they’re asking permission to keep burning coal here and send that energy eastward.

They built all that transmission, no Commission I’ve seen has ever found a transmission plan they didn’t like and roll over for, and now we’re paying for it. Rate increases anyone? Are you paying attention to what’s pushing those rates up?

Why ever would I say that it’s all about selling coal? Well… there’s a bit of a pattern going here. There was the Chisago project, starting in 1996 and three iterations in Minnesota and Wisconsin, not to mention the WRAO report:

WRAO laid out many transmission lines and the Arrowhead transmission project, circa 1999, was selected as the be all and end all of transmission after many hearings were held, one hearing in Minnesota and THREE before Wisconsin PSC, the price kept going UP, UP, UP!

But then on September 8, 2001, a meeting with likely intervenors to see if they could be convinced to “approve” of the SW Minnesota 345kV line, remember that, Commissioner Matt Schuerger? I pointed out all that coal lined up in the SW MN 345kV study… and from there on to the SW MN 345kV line, part of ABB plan for coal:

Don’t ya just love that name? It says it all. Why the ABB Lignite Vision 21 Transmission Study? The opening paragraph, linked above, DOH! says:

The SW MN 345kV line was the part that’s running east to west on the lower part of that yellow map, from Split Rock sub to Lakefield Junction. Some claimed it was an “It’s for WIND!” line, but that’s a lie, just read that ABB study again. The powerflows showed that it wasn’t to carry energy off of Buffalo Ridge, there was just 213-302 MVA coming off Buffalo Ridge into the over 2,000 MVA capacity line:

How stupid do they think we are? Well, money talked, and that money ruled the day. That SW MN 345kV line and the TRANSLink Settlement Agreement and 2005 Transmission Omnibus Bill from Hell (and changes to Minn. Stat. 117.189) laid the groundwork to bring us $2+ BILLION of CapX 2020:

And then the MISO MVP 17 project portfolio, now over $6 BILLION:

And then they have the audacity to suggest we need MORE transmission?

Upper Midwest utilities to study transmission grid in light of ambitious carbon reduction goals

CapX 2050 Vision Study

So please explain how selling coal generated electricity on the MISO market is consistent with carbon reduction goals?

What a crock…

WOW!  Who knew this many people would turn out, well, after all, it is Association of Freeborn County Landowners, talk about an active, thriving bunch!  What an incredible job of organizing, lining up live auction donations, oh, and making pudding shots… ja, I’m an old fart, jello shots bring back memories, but pudding? This group has shown up, and worked together to be heard — each and every one of you has made the difference in this groundbreaking challenge to Freeborn Wind’s application.  Keep up the good work!  And thank you!!!

And of course, the satellite office:

This morning, pelicans on the lake!  How cool is that!  This is the view out the office window:

And it took 2+ years, but I think I’ve finally got the camper kitchen figured out.  Before last trip added the Camp Chef stove, and this trip, added a table for the stove, and Alan made leg extensions for the prep table, and voila, a workable kitchen! Everything in its place and a place for everything.

p.s. phone signal is great!

SPP Map 2013

As if they don’t exist?  Yes, and that’s because they don’t.  That’s because they’re transmission projects in their own minds, and not in reality.

What?  SPP, the Southwest Power Pool, dissing Clean Line?  See for yourself!  It’s as simple as doing a simple search of the SPP planning reports.

We know, Clean Line is all about Clean Line, but there’s a significant disconnect between what Clean Line is saying about SPP, claiming “approval” of its projects and incorporation of those projects into SPP’s plans, and the reality of what shows up in those plans.  Or more correctly, what DOESN’T show up in those plans:

CLEAN LINE IS ABSENT!

PLAINS & EASTERN CLEAN LINE IS ABSENT!

GRAIN BELT EXPRESS CLEAN LINE IS ABSENT!

Whadda ya mean?  Well, on November 19, 2012, Plains & Eastern Clean Line sent out this press release:

SPP Transmission Working Group approves Plains & Eastern Clean Line reliability studies

This press release was EVERYWHERE, with Clean Line jubilant, jumping up and down, so excited and so elated, and stated that:

The Southwest Power Pool’s (SPP) Transmission Working Group today unanimously passed a motion accepting that the Plains & Eastern Clean Line reliability studies completed to date have met the coordinated planning requirements.

And went on to say (emphasis added) that:

Clean Line is also pleased to announce that it recently submitted the Plains & Eastern Clean Line and Grain Belt Express Clean Line projects, both +/- 600 kV high voltage direct current transmission projects capable of transmitting 3,500 MW from the SPP footprint to external-to-SPP sinks, in each of the ITP20 Futures 1 through 4. The objective of ITP20 is to develop an EHV backbone (345 kV and above) transmission plan for a 20-year horizon. The assessment will identify a robust transmission plan that is capable of reliably and economically providing deliverability of energy to the SPP market while enabling policy initiatives. The current ITP20 process is the second Integrated Transmission Planning Year 20 Assessment (ITP20). The assessment is conducted in accordance with the SPP Open Access Transmission Tariff (OATT) Attachment O, and the approved ITP Manual. The assessment begins in January 2012 and is scheduled to be finalized in July 2013.

Here’s that 2013 ITP 20:

2013 ITP20 Report – Southwest Power Pool

Now check out the map of their ITP20 projects in this report — do you see either the Plains & Eastern or Grain Belt mentioned above on this map:

SPP 2013 ITP20 Consolidated Portfolio 1Nope, neither do I.  I did a search of the narrative, and “Clean Line” isn’t even mentioned once!

And there are no ITP20s after that 2013 one above, either HERE on the ITP Assessments page or HERE on the ITP20 Documents page!

Oh, OK, so what about the SPP Planning and SPP’s STEP (not unlike the MTEP and RTEP!):

2015_STEP_Report

Do a search — nada… so I tried a search on “transmission” and blew up the computer.  So the search function works and in this report also, there’s no mention of Clean Line whatsoever, be it Plains & Eastern Clean Line or Grain Belt Clean Line or just plain ol’ Clean Line.

And there’s nothing here either:

2014 ITPNT Report

It’s only in the 2015 ITP10 SCOPE that there’s any mention of “Clean Line” and it’s only the Plains & Eastern Clean Line, not both, AND it’s only for sensitivity analysis.  This is not being included as a project, contemplated or promoted.

2015 ITP10 Scope Final MOPC

And in the resulting 2015 ITP10?  A mention in the list of sensitivities, and then three mentions on p. 103:

Final_2015_ITP10_Report_BOD_Approved_012715

And in the SPP 2015 Final Near Term Assessment, not a mention:

Final_2015_ITPNT_Assessment_BOD_Approved

When it comes to the scope of their next ITP10, Clean Line disappears, not even one mention, nada, again, not even an honorable mention as a “sensitivity” in the scope:

2016_ITPNT_Scope

Meanwhile, Illinois is holding “public hearings” that are very limited for what a large project this is, and very odd, considering that there are pending Motions for Reconsideration in this docket (Grain Belt Express Docket #15-0277 online at ICC’s e-docket system at www.icc.illinois.gov).

Public hearings tonight and tomorrow in Illinois:

ILL Hearings

I’d hope that Illinois, Missouri, Texas, Oklahoma, Arkansas and Tennessee pay attention to this lack of incorporation of any Clean Line project into SPP Planning!

Oh, and of course, the DOE should be paying attention!  Hey Office of Electric Deliverability and Energy Reliability, are you paying attention?

 

.
The miracle was he was brought to the hospital, treated, and released. WHEW!

SkydiverHitsLines
Who would hold an event with fly-ins of any type next to a big honkin’ transmission line?

 

From Scripps Channel 5 News
Skydiver Treated, Released From Hospital After Hitting Powerlines

And another version:

And in the Winchester Herald Chronicle:

Skydiver lines jolts Memorial Day event landing in power

Posted on Monday, May 25, 2015 at 9:27 am

STAFF WRITER courtney stachel

A skydiver drifting into a power line from a wind gust Saturday at the Red, White and You Memorial Day event in Winchester was followed by a happy ending when word was given that he had been treated and released from the hospital.

More than 400 spectators witnessed the incident when skydiver John Pitts, of the Fly It Like You Stole It skydiving team, was the first of three divers to exit an airplane and came down toward the ground gracefully while the National Anthem was being played.

A wind gust hit Pitts, causing him to drift into the electrical lines where he was left hanging for less than a minute. He dropped from the lines and fell onto a rocky area next to Tims Ford Lake.

Zachary Colescott, Winchester Municipal Airport manager, said right after the fall that Pitts was conscious and being airlifted.

Colescott said the team was concerned about the wind flow the day of the event.

“That was one thing we were worried about was the wind — being so close to the water and the power lines,” he said. “I’m really glad he is okay.”

Despite the scary interruption to the show, acclaimed country singer Lee Greenwood went on to perform as scheduled.

The event lasted all day and held plenty of entertainment for spectators, including the traveling Vietnam memorial wall, musical entertainment and a boat parade.

Jayson Davis, Moore-Cortner Funeral Home family services counselor, said the outcome at the event was surprising.

“There were a lot more people who came out than we expected,” he said. “I’m proud that so many people came out to enjoy the day with us.”

Greenwood was the main attraction. He spoke from the heart in a talking to the Herald Chronicle about small town U.S.A. and how he was looking forward to coming to Winchester and preforming.

“I love the small town flavor as it reminds me how I grew up in California,” he said. “Little towns are becoming big towns, and big towns are becoming big cities. Somewhere in the transition, we are losing the face of America. Winchester, Tennessee, is a reminder of all that is good with the United States.”

For Greenwood, Memorial Day provided the perfect opportunity to spread his message of patriotism.

“Memorial Day is not just about the good food, drinks and fireworks, which thrills the crowds — it’s about remembering those who have sacrificed through the years to give us that chance,” he said. “There are memorials all across the nation that bear witness to the struggle America has had in gaining and maintain our independence. It’s that thought I reflect on when I sing and when we observe this holiday.”

SkydiverHitsLines2